How Quiet Should a Recording Studio Be? Understanding Noise Criteria (NC)
In this article
Technical contribution from On-Site Acoustic Testing (OSAT USA). Editorial disclosure: OSAT USA and The Audio Magazine are under common ownership.
There is a substantial difference between the electronic noise floor of a recording chain and the acoustic noise floor of the room in which a microphone is operating. Replacing a preamp with a quieter model will not eliminate the rumble of an air handler or the hiss of a supply diffuser. Before spending money on quieter electronics, establish which part of the system is limiting the recording.
Why a single dBA number is insufficient
A-weighting reduces the contribution of lower frequencies to an overall sound level. That is useful for many purposes, but it can obscure the spectral balance of a room. A low-frequency fan or compressor component may be clearly audible on a vocal or a quiet acoustic instrument even when the overall A-weighted number appears unremarkable.
Noise Criteria (NC) evaluates octave-band sound pressure levels against a family of reference curves. In the conventional NC method the bands from 63 Hz to 8 kHz are considered, and the measured spectrum is compared with the applicable curves. The rating is governed by the highest curve required to contain the spectrum, subject to the adopted procedure. The band controlling the rating is valuable diagnostic information.
NC is not the same thing as dBA
NC 20 does not mean 20 dBA. It is a curve-based rating. Two rooms with a similar overall dBA reading may exhibit very different octave-band spectra and therefore different noise character. NC also does not fully describe infrasonic noise, strong discrete tones, temporal variation or vibration. For demanding recordings it may be appropriate to examine lower-frequency bands, time histories or narrowband spectra as well.
Choosing a target
Very quiet recording and broadcast rooms are often designed around stringent criteria, such as NC 15–25, depending on the function, project specification and measurement procedure. Control rooms, rehearsal spaces and editing suites can have different requirements. These figures are illustrative design objectives, not a universal building-code requirement. The source being recorded, microphone distance, gain structure and intended dynamic range all matter. A project acoustician should establish the actual criterion.
Measure the room under representative conditions
- Identify the intended recording position and additional representative positions.
- Turn off monitors and deliberately generated test signals. Document what equipment is operating.
- Measure with ventilation and mechanical systems in their normal operating condition. Compare other modes where feasible and safe.
- Use an appropriately calibrated sound level meter or measurement system with sufficiently low self-noise and octave-band capability. A system’s own noise floor can be a serious limitation in a very quiet room.
- Record octave-band levels, measurement duration, equipment states and relevant events. Repeat at different times if conditions vary.
A measurement microphone and audio interface can help identify trends, but absolute acoustic levels require calibration of the complete measurement chain. An uncalibrated DAW meter in dBFS does not report dB SPL. See TAM’s spectrum analyzer guide for the distinction between display types.
Diagnosing likely noise sources
| Observed signature | Possible cause to investigate |
|---|---|
| Steady low-frequency rumble | Fan, compressor, pump, traffic or structural vibration. |
| Mid/high-frequency hiss | Air turbulence at a diffuser, damper or restriction. |
| Distinct narrowband tone | Rotating machinery, motor, transformer or electronic interference. |
| Intermittent level changes | HVAC cycling, external activity, plumbing or equipment operation. |
| Noise present only in the electrical recording | Microphone self-noise, preamplifier noise, grounding or interference. |
These are hypotheses, not diagnoses. Similar spectra can arise from different causes. Change one operating condition at a time when practical and compare the results. Do not disable essential ventilation or safety systems to make a room seem quieter.
For a more detailed diagnostic workflow, see Recording Studio HVAC Noise: How to Identify the Source Before Replacing Equipment.
Specify performance rather than a particular product
Quiet air conditioning requires attention to airflow, pressure drop, equipment selection, duct routing, isolation and maintenance. A fan marketed as quiet can still create excessive noise in the completed system. The installed room should be assessed with systems operating as intended. A before-and-after measurement can establish whether corrective work has actually improved the condition.
For related professional methods, see OSAT’s field measurement capabilities and methods. For electronic noise, see TAM’s microphone self-noise explanation.